%0 Journal Article %T Microbial Contamination of Dental Unit Waterlines among Dental Clinics of India- An In vitro Study. %A Kengadaran S %A Vikraman R %A Indumathi KP %A Sundaragopal AK %A Adiraju VA %A Anusha D %J Indian J Dent Res %V 35 %N 1 %D 2024 Jan 1 %M 38934755 暂无%R 10.4103/ijdr.ijdr_463_22 %X BACKGROUND: Dental Unit Water Line (DUWL) deliver water to different handpieces in a dental unit. The water in DUWL circulates in a closed system, where it is taken from a container. The quality of dental water is of considerable importance since patients and dental staff are regularly exposed to water and aerosols generated from dental equipment. Output water from DUWLs may be a potential source of infection for both dental health care personnel and patients.
OBJECTIVE: To assess the microbial contamination in the DUWL among dental clinics in Chennai.
METHODS: An in vitro study was conducted on 60 water samples from 20 dental clinics in Chennai in December 2019. Water samples were collected from three different sources of the Dental unit according to ADA guidelines. The collected samples were assessed for the presence of Aspergillus, Acinetobacter, Pseudomonas aeruginosa, and Legionella by agar plate method. The data were analysed using SPSS software version 20.
RESULTS: Legionella was the most prevalent microorganism with 70% prevalence in a three-way syringe and 50% in scaler and airotor, followed by Pseudomonas aeruginosa and Acinetobacter with 10% prevalence in scaler and airotor and Aspergillus with a prevalence of 10% in the three-way syringe.
CONCLUSIONS: Most of the dental units were contaminated with Aspergillus, Legionella, Pseudomonas aeruginosa and Acinetobacter which pose a serious threat to the patients as well as the dentists.