%0 Review %T Review on descaling and anti-scaling technology of heat exchanger in high-salt wastewater thermal desalination. %A Wu Z %A Yan Z %A Zhang Q %A Zhu Y %A Luo M %A Zhou D %J Water Sci Technol %V 88 %N 8 %D 2023 Oct %M 37906460 %F 2.43 %R 10.2166/wst.2023.325 %X Thermal desalination evaporation of high-salt wastewater has been widely used in industry because of the proposed concept of 'zero liquid discharge'. However, due to the high content of Ca2+ and Mg2+ in high-salt wastewater, the heat exchanger, as the main treatment equipment, suffers from serious scaling problems. This review presents descaling and scale inhibition technologies of high-salt wastewater. The advantages and disadvantages of various technologies are summarized and analyzed to provide theoretical support for the research of descaling and anti-scaling of heat exchangers with high-salt wastewater. In future industrial development, the synergistic application of electromagnetic water treatment technology and scale inhibitors can significantly improve the anti-scaling effect, which can reach over 95% stably. Furthermore, the addition of a physical field can also expand the application range of scale inhibitors.